Type: | Ring Network Switch Equipment |
---|---|
Structure: | Protection |
Certification: | ISO9001:2000, CCC |
Form: | All- packaged Type |
Operation Voltage: | Low Voltage |
Size: | 1 Uint |
Customization: |
---|
Suppliers with verified business licenses
Ellumi-3 is a new generation of secondary distribution switch equipment with the feature of SF6 fully insulated, fully enclosed, extensible and maintenance-free. It's designed and developed, manufactured by SCE and has passed the type test by China National Center for Quality Supervision and Test of Electrical Apparatus Products and it's the first choice for distribution in urban and rural area. It can meet the different requirements for power distribution configuration.
1,With load switch, load switch +fuse combination electrical appliances circuit breaker functional unit,flexible for various complete schemes;
2,There are two types of structure for option,common compartment type and external bus expansion type. which can realize flexible combination of various schemes:
3,Small size.light weight,single unit dimension 500x1000x1750mmconvenient for transportation,handling and installation
4,Very suitable for use in places with verytight space requirements such as wind turbine tower.
5,It is easy to operate.safe to use and easy tomaintainno need maintenance for 30 years:
6,Switchgear is fully sealed,without any exposed live partsand can operate in harsh environment for long period.
No. | Technical Parameters | Unit | Data | ||||
1 | Rated voltage | kV | 40.5 | ||||
2 | Rated frequency | Hz | 50 | ||||
3 | Insulation level | Power frequency withstand voltage | kV/1min | Phase to earth, phase to phase between open contacts of breaker 95 Between open contacts of disconnecting switch 118 |
|||
Rated lightning impulse withstandvoltage(peak) | kV | Phase to earth, phase to phase between open contacts of breaker 1855 Between open contacts of disconnecting switch 215 |
|||||
4 | Rated current | A | 630 | 1250 | 2000 | 2500 | |
5 | Rated short-circuit breaking current | kA | 25/31.5 | ||||
6 | Rated short-time withstand current | kA/4s | 25/31.5 | ||||
7 | Rated peak withstand current | kA | 63/80 | ||||
8 | Rated short-circuit ciosing current | kA | 63/80 | ||||
9 | Rated inflation pressure(gauge pressure at 20ºC) | MPa | 0.13 | ||||
10 | Min. working pressure(gauge pressure at 20ºC) | 0.12 | |||||
11 | Mechanical endurance | Circuit breaker | Freq | 10000 | |||
3 position switchgear | 3000 | ||||||
12 | Protection level | Sealed gas box | IP67 | ||||
Switchgear | IP4X | ||||||
13 | Rated operation sequence | O - 0.3s - CO - 180s - CO | |||||
14 | Annual gas leakage rate | ≤0.01% |